Nominal diameter: DN20 ~ 450mm
Nominal pressure: PN1.0 ~ 2.5MPa
Medium: Water
Temperature: 0 ~ 80 ℃
Flange Standard: GB / T17241.6, GB / T9113
Test Standard: GB / T13927 , API598
300X slow closing check valve is installed in the high-rise building water supply system and other water supply pump outlet, to prevent media backflow, water hammer and water hammer phenomenon of intelligent valves. The valve combines electric valve, check valve and water hammer eliminator three functions, which can effectively improve the water supply system safety and reliability. And will slow open, fast closed, slowly closed to eliminate the technical principle of water hammer integration, to prevent open pump water hammer and pump water hammer. Just operate the pump motor hoist button, the valve can be automatically opened and closed in accordance with the pump operating procedures, flow, pressure loss, for the following 600 caliber valves.
300X slow-closing check valve by
the main valve, one-way valve, needle valve, ball valve, microfilter
and pressure gauge composed of hydraulic control system. The use of
hydraulic automatic operation, the main valve can be opened or closed
speed. Optional 300X slow closing check valve can prevent water Chung
blows produced in order to achieve the effect of slow closing
silencer. The hydraulic control valve products use hydraulic
self-control, does not require other devices and energy, easy
maintenance, open and slow and steady closure. 300X slow closing check
valve series valve products are widely used in high-rise buildings,
living areas and other water supply pipe network systems and urban water
supply projects.
300X slow-closing check valve scope
Current
hydraulic control valves are widely used in petrochemical, chemical,
gas, natural gas, liquefied petroleum gas, HVAC industry and general
industry.
300X slow closing check valve works
When
water is supplied from the inlet side, the water passes through the
microfilter, the needle valve, the check valve into the main valve
control room and then through the ball valve to the downstream. Because
the needle valve opening is less than the ball valve opening, that is,
the main valve control room drainage speed greater than the inlet speed,
so the control room pressure decreases, acting on the main valve plate
inlet pressure to open the main valve to the downstream water
supply. When the pipeline stops water supply, if the downstream water
starts to flow back, a part of the backflow water enters the main
control room through the ball valve. Due to the function of the one-way
valve, the backflow water can not flow out from the main control room,
causing the main control room to gradually increase pressure and
gradually close the main valve .
The main form of connection size
DN | 20 | 25 | 32 | 40 | 50 | 65 | 80 | 100 | 125 | 150 | 200 | 250 | 300 | 350 | 400 | 450 |
L | 150 | 160 | 180 | 200 | 203 | 216 | 241 | 292 | 330 | 356 | 495 | 622 | 698 | 787 | 914 | 978 |
H1 | 106 | 106 | 106 | 137 | 137 | 145 | 178 | 232 | 286 | 318 | 413 | 502 | 600 | 638 | 677 | 677 |
H | 172 | 172 | 172 | 225 | 225 | 270 | 289 | 375 | 420 | 570 | 722 | 769 | 906 | 1025 | 1027 | 1027 |